Legrand 1597TRW

Legrand 1597TRW Tamper Resistant GFCI Wall Outlet User Manual

Model: 1597TRW

Introdución

This manual provides detailed instructions for the safe installation, operation, and maintenance of the Legrand 1597TRW Tamper Resistant GFCI Wall Outlet. This device is part of the radiant collection, designed to offer reliable electrical protection in residential and commercial environments. Please read these instructions thoroughly before beginning installation or use.

Información de seguridade

WARNING: Risk of electric shock. May cause serious injury or death. Turn off power at the circuit breaker or fuse box before installation.

  • Always disconnect power at the service panel before working with electrical wiring.
  • Installation must be performed by a qualified electrician or in accordance with all local and national electrical codes.
  • Non o instale en lugares húmidos a menos que estea especificamente homologado para tal uso.
  • Asegúrate de que todas as conexións dos cables estean seguras e debidamente illadas.
  • Test the GFCI outlet monthly to ensure proper operation.

Contido do paquete

Comprobe que todos os compoñentes estean presentes antes de comezar a instalación:

  • Legrand 1597TRW Tamper Resistant GFCI Wall Outlet (White)
  • Parafusos de montaxe
  • Manual de instrucións (este documento)

Note: A screwless wall plate is not included and must be purchased separately.

Instalación

Follow these steps for proper installation of your GFCI outlet:

  1. Apagar a enerxía: Locate the circuit breaker or fuse that supplies power to the outlet box. Turn it off completely. Verify power is off using a voltagprobador.
  2. Eliminar a antiga toma: Carefully remove the existing wall plate and outlet from the electrical box. Disconnect the wires from the old outlet, noting which wires were connected to the "LINE" and "LOAD" terminals.
  3. Identificar os cables:
    • LINE Wires: These wires bring power from the circuit breaker to the GFCI outlet.
    • LOAD Wires: These wires carry power from the GFCI outlet to other downstream receptacles or devices that you want to protect. If there are no downstream receptacles, cap the LOAD wires individually.
    • Fío de terra: Typically bare copper or green insulated.
  4. Connect Wires to GFCI:
    • Conecta o LIÑA wires to the terminals marked "LINE" on the GFCI outlet.
    • Conecta o CARGA wires to the terminals marked "LOAD" on the GFCI outlet.
    • Conecta o cable de terra to the green ground screw.

    Importante: The Legrand 1597TRW features a feed-thru wiring configuration that allows the GFCI to protect downstream receptacles. It also prevents line-load reversal miswire, meaning there will be no power to the face or downstream receptacles if wired incorrectly. An auto-ground clip assures a positive ground to a metal box.

  5. Montar a toma de corrente: Carefully fold the wires into the electrical box and secure the GFCI outlet to the box using the provided mounting screws.
  6. Instalar placa de parede: Attach the screwless wall plate (not included) over the GFCI outlet.
  7. Restaurar enerxía: Volve a conectar o interruptor.
Legrand 1597TRW GFCI Outlet, front view

Imaxe: Fronte view of the Legrand 1597TRW Tamper Resistant GFCI Wall Outlet. This image shows the two tamper-resistant receptacles, the TEST button (black), and the RESET button (red).

Operación

The GFCI outlet is designed to protect against electrical shock by quickly shutting off power if a ground fault is detected.

  • Botón RESET: After installation or a power outage, press the red RESET button to restore power to the outlet.
  • Botón TEST: Press the black TEST button to simulate a ground fault. The GFCI should trip, and power to the outlet will be cut off. This confirms the GFCI is functioning correctly.

Probas mensuais:

It is recommended to test your GFCI outlet monthly to ensure it is providing continuous protection. To test:

  1. Enchufe alamp or other device into the GFCI outlet and turn it on.
  2. Press the black TEST button. The lamp should turn off, and the red RESET button should pop out.
  3. Press the red RESET button. The lamp debería volver acenderse.
  4. Se o lamp does not turn off or on as described, the GFCI may be faulty and should be replaced.

Mantemento

The Legrand 1597TRW GFCI outlet requires minimal maintenance. Regular testing is the primary maintenance procedure.

  • Keep the outlet clean and free from dust and debris.
  • Do not paint over the GFCI outlet or its buttons, as this can impair operation.
  • If the GFCI trips frequently without an apparent cause, consult a qualified electrician to inspect your wiring.

Resolución de problemas

Problema Causa posible Solución
O GFCI non se reiniciará.
  • No power to the GFCI.
  • Detectouse falla a terra.
  • Line-load reversal miswire.
  • Faulty GFCI.
  • Comprobar o interruptor automático.
  • Unplug all devices from the GFCI and downstream outlets. Try to reset. If it resets, plug devices back in one by one to identify the faulty device.
  • Verify wiring connections (LINE to LINE, LOAD to LOAD).
  • Replace the GFCI.
O GFCI dispónese con frecuencia.
  • Faulty appliance/device.
  • Moisture in the circuit.
  • Damaged wiring.
  • Identify and remove the faulty appliance.
  • Ensure the environment is dry.
  • Consulte cun electricista cualificado para inspeccionar o cableado.
Sen corrente na toma de corrente.
  • O GFCI disparou.
  • O interruptor automático disparou.
  • Cableado incorrecto.
  • Preme o botón RESET.
  • Comprobe e reinicie o interruptor automático.
  • Verificar as conexións do cableado.

Especificacións

  • Modelo: 1597TRW
  • Marca: Legrand
  • Cor: Branco
  • Ampera: 15 Amps
  • Voltage: 125 voltios
  • Total de tomas de corrente: 2
  • Tipo de conector: Nema 5-15
  • Material: Metal
  • Características: Tamper Resistant, Auto-Ground Clip, Feed-Thru Wiring, Line-Load Reversal Miswire Prevention
  • UPC: 680147085438
  • ASIN: B079LTP7Y5

Garantía e Soporte

Legrand products are designed and manufactured to the highest quality standards. For specific warranty information, please refer to the documentation included with your purchase or visit the official Legrand website. For technical support or further assistance, please contact Legrand customer service.

Contact information for Legrand can typically be found on their official websitio ou embalaxe do produto.

© 2024 Legrand. Todos os dereitos reservados. A información deste manual está suxeita a cambios sen previo aviso.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.