Sargent 1560

Sargent 1560 Electromagnetic Surface Mount Door Holder

Manual de instrucións

Model: 1560 | Brand: Sargent

1. Introdución

The Sargent 1560 Electromagnetic Surface Mount Door Holder is designed to securely hold fire and smoke barrier doors in an open position. Upon activation of a remote smoke detector, fire alarm system, or other contact device, the electromagnet releases the door, allowing it to close and contain the spread of fire and smoke. This manual provides essential information for the safe and correct installation, operation, and maintenance of your door holder.

2. Información de seguridade

AVISO: Risco de descarga eléctrica.

  • Always disconnect power to the circuit before attempting any installation, wiring, or servicing of this device.
  • Installation must be performed by qualified personnel in accordance with all applicable local and national electrical codes and regulations.
  • Asegúrese de que o voltage supply (120VAC, 24VAC/DC, or 12VDC) is used as specified for the unit. Incorrect voltage can cause damage to the unit and pose a safety hazard.
  • Non poñas en funcionamento o dispositivo se parece estar danado.

3. Configuración e instalación

Proper installation is crucial for the reliable operation of the Sargent 1560 door holder. Follow these steps carefully.

Sargent 1560 Electromagnetic Surface Mount Door Holder components

This image displays the main electromagnet unit (left) and the separate armature plate (right), which is designed to be mounted on the door.

  1. Determinar a localización de montaxe: Identify the desired open position for the door. The electromagnet unit should be mounted on the wall or floor, and the armature plate on the door, ensuring they align perfectly when the door is in the open position.
  2. Mount the Electromagnet Unit: Securely attach the electromagnet unit to the wall or floor using appropriate fasteners (not included, typically). Ensure the mounting surface is stable and capable of supporting the unit's weight and holding force.
  3. Mount the Armature Plate: Attach the armature plate to the door. The plate must be positioned so that its face makes full and flush contact with the electromagnet's face when the door is in the desired hold-open position. Adjustments may be necessary to achieve optimal alignment.
  4. Conexións de cableado:
    • Ensure power is disconnected at the circuit breaker before proceeding.
    • Connect the power supply wires to the terminals on the electromagnet unit. Refer to the specific wiring diagram provided with your unit for detailed connections.
    • Verifique que o voltage supplied matches the voltage rating of your Sargent 1560 unit (120VAC, 24VAC/DC, or 12VDC).
    • Todo o cableado debe cumprir cos códigos eléctricos locais.
  5. Proba de funcionamento: Restore power to the circuit. Manually open the door to the hold-open position. The electromagnet should engage and hold the door. Activate the fire alarm system or release mechanism to ensure the door releases and closes properly.

4. Instrucións de funcionamento

The Sargent 1560 door holder operates automatically once installed and wired correctly.

  • Holding the Door: When the door is opened to the position where the armature plate makes contact with the energized electromagnet, the magnetic force will hold the door securely in place.
  • Releasing the Door: The door holder is designed to release the door when the power supply to the electromagnet is interrupted. This interruption is typically triggered by:
    • Activation of a fire alarm system.
    • Activation of a smoke detector.
    • Manual activation of a release switch (if installed).
  • Upon release, the door will close under the action of its own closing mechanism (e.g., a door closer), preventing the spread of fire and smoke.

5. Mantemento

Regular maintenance ensures the continued reliability and performance of your door holder.

  • Inspección periódica: Visually inspect the electromagnet unit and armature plate at least annually for any signs of wear, damage, corrosion, or loose components.
  • Limpeza: Keep the contact surfaces of both the electromagnet and the armature plate clean and free from dust, dirt, paint, or other debris. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents. A clean contact surface ensures maximum magnetic holding force.
  • Comprobación do cableado: Periodically check all electrical connections to ensure they are secure and that the wiring insulation is intact and undamaged.
  • Proba funcional: Test the door holder's release function regularly (e.g., monthly or as required by local fire codes) by activating the associated fire alarm or smoke detection system to ensure the door releases and closes properly.

6 Solución de problemas

If your Sargent 1560 door holder is not functioning as expected, refer to the following troubleshooting guide:

ProblemaCausa posibleSolución
Door not holding open
  • No power to electromagnet
  • Dirty or obstructed contact surfaces
  • Misalignment between electromagnet and armature plate
  • Vol. incorrectotage subministración
  • Check circuit breaker and wiring for power.
  • Clean electromagnet and armature plate surfaces.
  • Adjust mounting positions for proper alignment.
  • Verificar voltage coincide coas especificacións da unidade.
Door not releasing
  • Continuous power to electromagnet
  • Faulty release mechanism (e.g., smoke detector, fire alarm panel)
  • Wiring fault (e.g., short circuit)
  • Check wiring to ensure power is interrupted upon alarm activation.
  • Test the release mechanism independently.
  • Inspect wiring for damage or incorrect connections.

If the problem persists after attempting these solutions, contact a qualified technician or Sargent customer support.

7. Especificacións

  • Modelo: 1560 E
  • Marca: Sargento
  • Fabricante: ASSA ABLOY
  • Tipo de montaxe: Montaxe en superficie
  • Voltage Opcións: 120VAC, 24VAC/DC, 12VDC (Vol. específicotage depends on the model variant purchased)
  • Peso do artigo: Aproximadamente 8 libras
  • Aplicación: Fire and smoke barrier doors

8. Garantía e soporte

For detailed warranty information, technical assistance, or to purchase replacement parts, please refer to the official Sargent website or contact Sargent customer service directly. Keep your purchase receipt for warranty claims.

Documentos relacionados - 1560

Preview Instrucións de instalación do peche-soporte electromecánico SARGENT 2900 FIREGUARD
Guía de instalación detallada para o peche-soporte electromecánico SARGENT 2900 FIREGUARD, modelo 2980 Retén multipunto en aberto con brazo libre de oscilación. Inclúe os pasos para a montaxe, a instalación do brazo e do carril, os axustes e o cableado.
Preview Instrucións de instalación do montante con pechadura e sen resistencia ao lume Sargent L980S
Guía de instalación completa para o montante pechable sen clasificación de lume Sargent L980S, que detalla a montaxe paso a paso e a instalación do cilindro. Inclúe as especificacións do produto e información de seguridade de ASSA ABLOY.
Preview Sargent 1430/1431 Door Closer Installation Instructions
Comprehensive installation guide for Sargent 1430 and 1431 series door closers, including standard, parallel arm, and top jamb applications. Details spring adjustment, backcheck regulation, and use of accessories.
Preview SARGENT IN120/IN220 Exit Device Installation and Operational Guide
Comprehensive guide for installing and performing operational checks on SARGENT IN120 and IN220 Exit Devices. Includes battery installation, cover assembly, and functional testing procedures for access control systems.
Preview Instrucións de instalación do dispositivo de saída de varilla vertical de superficie Sargent FM8700/12-FM8700
Guía de instalación completa para o dispositivo de saída de varilla vertical de superficie Sargent FM8700 e 12-FM8700, que detalla as ferramentas, os elementos de fixación, a preparación da porta, a montaxe paso a paso, os axustes e o corte de carrís. Inclúe descricións textuais de diagramas e importantes avisos de seguridade.
Preview Catálogo de dispositivos de saída da serie 80 de SARGENT
Comprehensive catalog detailing the SARGENT 80 Series of exit devices, including rim, mortise, and vertical rod options. Features, specifications, fire ratings, windstorm certifications, and trim designs are covered for various applications.