Simplex S4099-9006

Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station

Modelo: S4099-9006

1. Introdución

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station. This device is designed to initiate a fire alarm signal when manually activated, contributing to the overall safety and security of a building's occupants.

The Simplex 4099-9006 is an IDNet addressable manual pull station with an integrated LED indicator, ensuring reliable communication within compatible fire alarm systems.

2. Información de seguridade

WARNING: Installation and servicing of this device must be performed by qualified personnel only, in accordance with all local and national electrical codes, and the National Fire Alarm and Signaling Code (NFPA 72).

  • Always disconnect power to the fire alarm control panel before installing or servicing the pull station.
  • Asegúrese de conectar a terra adecuada para evitar descargas eléctricas.
  • Do not paint over the pull station or obstruct its operation.
  • Test the pull station regularly as part of a comprehensive fire alarm system testing schedule.
  • This device is not intended for outdoor use unless specifically rated for such environments.

3. Produto rematadoview

The Simplex 4099-9006 is a robust, red-colored manual fire alarm pull station featuring a double-action mechanism (push then pull). It includes an integrated LED indicator for status feedback.

Simplex 4099-9006 Double Action Fire Alarm Pull Station with installation instructions

Figure 3.1: Simplex 4099-9006 Double Action Fire Alarm Pull Station. This image displays the front of the red pull station with "FIRE ALARM" and "PUSH PULL DOWN" labels, alongside a detailed instruction sheet for installation and mounting, and a small bag of mounting hardware.

Os compoñentes clave inclúen:

  • Controlador de activación: The "PUSH PULL DOWN" mechanism used to initiate an alarm.
  • Indicador LED: Provides visual status of the device (e.g., normal, alarm, trouble).
  • Bloque de terminales: For connecting to the fire alarm control panel's IDNet circuit.
  • Mounting Plate/Housing: Secures the device to a standard electrical box or surface.

4. Configuración e instalación

The Simplex 4099-9006 pull station can be installed using either single-gang or two-part mounting methods, typically on a standard 4-inch square electrical box (not supplied).

4.1 Comprobacións previas á instalación

  • Verify that the fire alarm control panel is powered off.
  • Ensure the mounting location is clean, dry, and meets local code requirements for height and accessibility.
  • Confirm all necessary tools and hardware are available (e.g., screwdriver, wire strippers, mounting screws).

4.2 Procedementos de montaxe

Refer to the installation diagrams provided with the product and shown in Figure 3.1 for visual guidance.

4.2.1 Single-Gang Mounting

  1. Secure the pull station directly to a standard single-gang electrical box.
  2. Ensure the device is flush with the wall surface.

4.2.2 Two-Part Mounting

  1. Install the backbox or mounting plate first, typically a 4-inch square electrical box.
  2. Mount the pull station assembly onto the installed backbox.
  3. This method may be used for flush trim or surface mounting applications.

4.3 Cableado

The 4099-9006 is an IDNet addressable device. Connect the pull station to the IDNet circuit of the fire alarm control panel using appropriate gauge wiring, following the wiring diagram provided on the device or in its specific installation sheet. Ensure polarity is correct.

  • Connect the incoming and outgoing IDNet circuit wires to the designated terminals.
  • Asegúrate de que todas as conexións estean seguras e libres de curtos.

4.4 Despois da instalación

  • Once installed and wired, restore power to the fire alarm control panel.
  • Verify the LED indicator on the pull station shows a normal operating status (typically a slow flash).
  • Perform a functional test of the pull station as described in the "Operating Instructions" section.

5. Instrucións de funcionamento

The Simplex 4099-9006 features a double-action activation mechanism to prevent accidental alarms.

5.1 Activating the Alarm

  1. EMPURRÓN: Firmly push the "PUSH" bar located at the top of the activation handle.
  2. PULL DOWN: Once the "PUSH" bar is depressed, pull the handle "PULL DOWN" until it latches in the alarm position.
  3. Upon activation, the pull station will send an alarm signal to the fire alarm control panel, and the integrated LED will illuminate steadily (or change to a rapid flash, depending on system programming) to indicate an alarm state.

5.2 Reinicio da estación de tracción

To reset the pull station after an alarm, a special key (not included with this specific model, as indicated by "No Key" in the product title, implying a different reset mechanism or system-level reset) or tool is typically required to return the handle to its normal, non-alarm position. For the 4099-9006, the reset mechanism is internal and does not require a key. Simply push the handle back into its original position. The fire alarm control panel must also be reset to clear the alarm condition from the system.

6. Mantemento

Regular maintenance ensures the reliable operation of your Simplex 4099-9006 pull station. All maintenance should be performed by qualified personnel.

6.1 Comprobacións de rutina

  • Inspección visual (mensual): Check for any physical damage, obstructions, or signs of tampering. Ensure the pull station is clean and clearly visible.
  • LED Status (Monthly): Verify the LED indicator is showing a normal operating status (e.g., slow flash).

6.2 Functional Testing (Annually or as per local codes)

Functional testing should be conducted by a certified fire alarm technician.

  1. Notify building occupants and the monitoring station before testing.
  2. Activate the pull station as described in "Operating Instructions".
  3. Verify that the fire alarm control panel receives the alarm signal and initiates appropriate responses (e.g., sounding alarms, notifying monitoring station).
  4. Reinicie a estación de control e o panel de control da alarma de incendios.
  5. Confirm the pull station returns to a normal operating state.

6.3 Limpeza

Limpar o exterior da estación de extracción cun pano suave eamp pano. Non empregue produtos de limpeza abrasivos nin disolventes, xa que poden danar o acabado ou os compoñentes internos.

7 Solución de problemas

This section addresses common issues you might encounter with the Simplex 4099-9006 pull station. For complex issues, contact a qualified fire alarm technician.

ProblemaCausa posibleSolución
Pull Station does not activate alarm.Incorrect activation procedure; wiring issue; device fault; control panel issue.Ensure proper push-then-pull action. Check wiring connections. Verify control panel status. Contact technician if problem persists.
LED indicator is off or shows trouble.No power; wiring fault; device fault; control panel trouble.Check power to the control panel. Inspect wiring for breaks or shorts. Consult control panel manual for trouble codes. Contact technician.
Falsa alarma.Accidental activation; faulty device; wiring issue.Reset the pull station and control panel. Inspect for physical damage or obstructions. If recurring, contact technician.
Pull station handle does not reset.Internal mechanism issue; debris.Ensure no debris is obstructing the mechanism. Gently attempt to push the handle back. If it remains stuck, the unit may need replacement.

8. Especificacións

CaracterísticaDetalle
Número de modeloS4099-9006
Tipo de produtoDouble Action Manual Fire Alarm Pull Station
MarcaSimplex
FabricanteSIMPLEX Grinnell
CorVermello
Método de activaciónPush then Pull Down
Key Requirement for ResetNo Key Required (Internal Reset)
ConectividadeIDNet Addressable
Características integradasIndicador LED
Peso do elemento0.5 libras (aprox. 8 onzas)
Dimensións do produto6 x 6 x 4 polgadas (aproximado)
UPC643485653004
Data de primeira dispoñibilidade21 de decembro de 2015
Simplex 4099-9006 product packaging boxSimplex 4099-9006 product packaging box with PID and Part No.

Figure 8.1: Product packaging for the Simplex 4099-9006, showing the brown cardboard box with product identification labels. The labels confirm PID 4099-9006 and Part No. 06501211.

9. Garantía e soporte

9.1 Información da garantía

This Simplex product is typically covered by a manufacturer's warranty against defects in materials and workmanship. Specific warranty terms and duration may vary. Please refer to the original purchase documentation or contact Simplex customer service for detailed warranty information.

Note: The product listing mentions "12 months warranty" and "30 days return if not satisfied". This information is from a third-party seller and may not reflect the official manufacturer's warranty. Always verify with the manufacturer.

9.2 Soporte técnico

For technical assistance, installation guidance, or troubleshooting beyond the scope of this manual, please contact a certified fire alarm technician or the manufacturer directly.

Simplex Customer Support: Please visit the official SimplexGrinnell websitio web ou consulte a embalaxe do produto para obter os datos de contacto.

Para consultas xerais, tamén podes consultar o Simplex brand page on Amazon.

Documentos relacionados - S4099-9006

Preview Estacións de alarma contra incendios manuais direccionables Simplex IDNet/MAPNET II: datos do produto
Información detallada sobre as estacións de alarma contra incendios manuais direccionables Simplex serie 4099, compatibles cos sistemas IDNet e MAPNET II. Características, especificacións, opcións de montaxe e selección de produtos para varios modelos, incluíndo opcións de acción simple, dobre acción (rompevidros e empurrar) e SEN AGARRE. Cumpre cos requisitos da ADA e está homologado por UL, ULC, FM e CSFM.
Preview Estacións manuais direccionables simplex: periféricos IDNet/MAPNET II
Explore as estacións de alarma contra incendios manuais direccionables Simplex, detallando as súas características, tipos de acción simple/dobre, opcións SEN AGARRE e compatibilidade cos sistemas IDNet/MAPNET II. Inclúe información de montaxe e especificacións.
Preview Simplex 2099 Series Single and Double Action Manual Fire Alarm Stations Datasheet
Datasheet for Simplex 2099 Series non-coded, non-addressable manual fire alarm pull stations. Covers features, operation types, application references, product selection, mounting options, and specifications.
Preview Simplex 4010ES: Systèmes de commande d'extinction automatique pour gicleurs
Guide technique Simplex 4010ES détaillant les modules de commande pour les systèmes d'extinction automatique par gicleurs, couvrant les modes déluge et préventif, avec spécifications, homologations et schémas de câblage.
Preview Simplex 4004 Fire Alarm Control Panel: Installation and Operation Instructions
Comprehensive guide for installing, operating, and programming the Simplex 4004 Fire Alarm Control Panel (FACP), including system overview, requirements, wiring, module descriptions, and troubleshooting.
Preview Simplex 4010ES Fire Control Unit Datasheet: Automatic Extinguishing, Deluge & Preaction Sprinkler Systems
Technical datasheet for the Simplex 4010ES Fire Control Unit, detailing its capabilities for automatic extinguishing, deluge, and preaction sprinkler system releasing control. Includes features, specifications, agency listings, and compatible components.