Simplex 4099 9006

Simplex 4099-9006 Addressable Manual IDNET Pull Station Instruction Manual

Modelo: 4099-9006

Introdución

This manual provides essential information for the proper installation, operation, and maintenance of the Simplex 4099-9006 Addressable Manual IDNET Pull Station. Please read this manual thoroughly before attempting any procedures to ensure safe and correct usage.

The Simplex 4099-9006 is designed for use in fire alarm systems to manually initiate an alarm. It is an addressable device, meaning it communicates its status and location to a compatible fire alarm control panel.

Información de seguridade

Instrucións de seguridade importantes:

  • A instalación e o mantemento deben ser realizados só por persoal cualificado.
  • Desconecte toda a enerxía antes de realizar o servizo.
  • Refer to all local and national electrical codes and fire safety regulations.
  • Non poñas en funcionamento o dispositivo se parece estar danado.
  • Asegúrese de conectar a terra adecuada para evitar descargas eléctricas.

Produto rematadoview

Simplex 4099-9006 Manual Pull Station

Figura 1: Fronte view of the Simplex 4099-9006 Addressable Manual IDNET Pull Station. The device is red with "FIRE ALARM" text at the top, a keyhole for resetting, and a black "PUSH" bar above a white "PULL DOWN" handle with a downward arrow. The Simplex logo is at the bottom.

The Simplex 4099-9006 is a single-action manual pull station designed for flush or surface mounting. It features a durable red housing and clear instructions for activation. The device includes a key-operated reset mechanism.

Configuración e instalación

Proper installation is crucial for the reliable operation of the pull station. Follow these steps carefully:

  1. Lugar de montaxe: Select a visible and accessible location, typically near exits, in accordance with local fire codes (e.g., NFPA 72). The handle should be between 42 and 48 inches (107-122 cm) above the finished floor.
  2. Cableado:
    • Ensure power to the fire alarm control panel is disconnected.
    • Connect the IDNET communication wiring to the designated terminals on the pull station. Refer to the wiring diagram provided with the device or the control panel manual for specific terminal assignments.
    • Maintain proper polarity.
  3. Montaxe:
    • Attach the pull station to a standard single-gang electrical box or a compatible surface mount box using the provided screws.
    • Ensure the device is securely fastened and level.
  4. Enderezo: The 4099-9006 is an addressable device. Set the address using the rotary switches or dip switches on the back of the unit, as per the fire alarm control panel's programming requirements. Consult the control panel's manual for address range and assignment procedures.
  5. Asemblea final: Secure the front cover of the pull station.
  6. Acenda e probe: Restore power to the fire alarm control panel and perform a functional test of the pull station as described in the "Operating" section.

Instrucións de funcionamento

The Simplex 4099-9006 is designed for straightforward operation during a fire emergency.

To Activate the Alarm:

  1. Locate the manual pull station.
  2. EMPUXE the black bar at the top of the activation mechanism.
  3. Immediately after pushing, TIRA PARA Abaixo the white handle firmly until it latches in the activated position.
  4. This action will send an alarm signal to the fire alarm control panel, initiating the building's alarm sequence.

To Reset the Pull Station:

After an alarm has been activated and the situation is resolved, the pull station must be reset. This requires a special key.

  1. Insert the Simplex reset key into the keyhole located at the top center of the pull station.
  2. Turn the key clockwise until the handle returns to its normal, non-activated position.
  3. Retire a chave.
  4. The fire alarm control panel must also be reset after the pull station has been restored. Refer to the control panel's manual for its specific reset procedure.

Mantemento

Regular maintenance ensures the continued reliability of your Simplex 4099-9006 pull station.

  • Inspección visual (mensual): Check for any physical damage, obstructions, or signs of tampering. Ensure the device is clean and visible.
  • Functional Test (Annually or as per local codes):
    • Notify building occupants and the monitoring station before testing.
    • Activate the pull station as described in the "Operating Instructions" section.
    • Verify that the alarm signal is received at the fire alarm control panel and that associated alarm functions (e.g., sirens, strobes) activate correctly.
    • Reinicie a estación de control e o panel de control da alarma de incendios.
    • Document all tests, including date, time, and results.
  • Limpeza: Usa un pano suave e seco para limpar o exterior. Non empregues produtos de limpeza abrasivos nin solventes.

Resolución de problemas

This section addresses common issues you might encounter with the Simplex 4099-9006 pull station.

ProblemaCausa posibleSolución
A estación de tracción non activa a alarma.
  • Not fully activated.
  • Problema de cableado.
  • Enderezo incorrecto.
  • Faulty device.
  • Ensure handle is pulled down completely until latched.
  • Check wiring connections and polarity.
  • Verify address setting matches control panel programming.
  • Contact qualified service personnel for inspection/replacement.
A estación de extracción non se pode restablecer.
  • Usouse unha chave incorrecta.
  • Mecanismo atascado.
  • Use the correct Simplex reset key.
  • Do not force. Contact qualified service personnel.
Control panel shows a trouble signal for the pull station.
  • Wiring fault (open/short).
  • Incorrect address.
  • Mal funcionamento do dispositivo.
  • Inspect wiring for damage or loose connections.
  • Verify address setting.
  • Contacte con persoal de servizo cualificado.

For issues not listed here, or if solutions do not resolve the problem, contact qualified fire alarm service personnel.

Especificacións

CaracterísticaDetalle
Número de modelo4099-9006
TipoEstación manual direccionable
Método de activaciónPush/Pull Down
Método de reinicioReinicio de teclas
CorVermello
Dimensións (aprox.)5.39 x 4.45 x 4.09 polgadas (dimensións do paquete)
Peso (aprox.)12.8 onzas (0.8 libras)
Fonte de enerxíaSystem Powered (Manual Activation)
CompatibilidadeSimplex IDNET Fire Alarm Control Panels

Información da garantía

Specific warranty terms for the Simplex 4099-9006 are typically provided at the point of purchase or can be obtained directly from Simplex or an authorized distributor. Generally, Simplex products come with a limited warranty covering defects in materials and workmanship under normal use and service.

For detailed warranty information, please refer to the documentation included with your purchase or visit the official Simplex websitio. Garda o comprobante de compra para reclamacións de garantía.

Soporte e Contacto

If you require technical assistance, have questions regarding installation, operation, or maintenance, or need to report a malfunction, please contact your authorized Simplex distributor or service provider.

For general inquiries, you may visit the official Simplex website or refer to the contact information provided in your system's overall documentation.

Nota: Do not attempt to repair the device yourself. Servicing should only be performed by qualified and authorized personnel.

Documentos relacionados - 4099 9006

Preview Estacións de alarma contra incendios manuais direccionables Simplex IDNet/MAPNET II: datos do produto
Información detallada sobre as estacións de alarma contra incendios manuais direccionables Simplex serie 4099, compatibles cos sistemas IDNet e MAPNET II. Características, especificacións, opcións de montaxe e selección de produtos para varios modelos, incluíndo opcións de acción simple, dobre acción (rompevidros e empurrar) e SEN AGARRE. Cumpre cos requisitos da ADA e está homologado por UL, ULC, FM e CSFM.
Preview Estacións manuais direccionables simplex: periféricos IDNet/MAPNET II
Explore as estacións de alarma contra incendios manuais direccionables Simplex, detallando as súas características, tipos de acción simple/dobre, opcións SEN AGARRE e compatibilidade cos sistemas IDNet/MAPNET II. Inclúe información de montaxe e especificacións.
Preview Simplex 2099 Series Single and Double Action Manual Fire Alarm Stations Datasheet
Datasheet for Simplex 2099 Series non-coded, non-addressable manual fire alarm pull stations. Covers features, operation types, application references, product selection, mounting options, and specifications.
Preview Simplex 4100ES Addressable Fire Detection and Control Panels: Features, Modules, and Specifications
Detallado máisview of the Simplex 4100ES Series Fire Control Panels, covering features, addressable device control, module selection, system operation, and technical specifications for fire detection and alarm systems.
Preview Simplex 4010ES Fire Control Units: Comprehensive Guide
Explore the features, specifications, and operational details of the Simplex 4010ES Addressable Fire Detection and Control Units. This guide covers basic system components, optional modules, and system compatibility for advanced fire safety solutions.
Preview Simplex 4090-9007 IDNet Signal IAM: Módulo direccionable para sistemas de alarma contra incendios
Especificacións técnicas detalladas e características do módulo direccionable individual (IAM) de sinal IDNet Simplex 4090-9007, deseñado para unha sinalización selectiva e un control de audio mellorados nos paneis de control de alarma contra incendios Simplex das series 4100ES, 4010ES, 4100U e 4008. Inclúe información sobre cableado, funcionamento e montaxe.