1. Introdución
The Vantec EEI 25-40/180 High-Efficiency Circulation Pump is designed to facilitate forced circulation within central heating systems. Equipped with an inverter and a processor, the pump automatically adjusts its power and pressure parameters to meet the specific demands of the system. This design ensures efficient and stable operation with minimal energy consumption.
Key operational characteristics include quiet performance, very low energy consumption (as low as 5 W), and resistance to corrosion, contributing to its durability and reliability in various heating and cooling applications.
2. Información de seguridade
Before installation, operation, or maintenance, carefully read and understand all instructions in this manual. Failure to follow these instructions may result in property damage, injury, or death. Ensure all electrical connections are performed by a qualified electrician in accordance with local regulations. Always disconnect power before performing any service or maintenance on the pump. Do not operate the pump if it is damaged or if any electrical components are exposed to moisture.
3. Contido do paquete
Verifique que todos os compoñentes estean presentes e non presenten danos ao desembalar:
- Vantec EEI 25-40/180 Circulation Pump
- Kit de atornillado
- Xuntas
- Cable de alimentación con enchufe

Image: The Vantec EEI 25-40/180 circulation pump shown with its included accessories, such as the power cable, screw fittings, and gaskets, all within its product packaging.
4. Configuración e instalación
Installation of the Vantec EEI 25-40/180 pump should be carried out by qualified personnel to ensure proper function and safety. The pump is designed for integration into existing or new central heating systems.
4.1. Instalación mecánica
- Ensure the system is depressurized and drained before installation.
- Mount the pump in the designated location, ensuring the flow direction matches the system. The pump has a spacing of 180 mm between connections.
- Use the provided screw fitting kit and gaskets to connect the pump to the system piping. The connection diameter is 1 1/2" - 1". Tighten connections securely to prevent leaks.

Image: The Vantec EEI 25-40/180 pump with its screw fittings installed, illustrating how it connects to system piping.

Imaxe: Unha detallada view of the screw fitting kit and gaskets provided for secure and leak-proof installation.
4.2. Conexión eléctrica
- Connect the provided power cable to the pump's electrical input.
- Plug the power cable into a suitable 230 V/50 Hz electrical outlet. Ensure the power supply is stable and meets the pump's requirements.

Image: The power cable with a standard plug, used to connect the pump to the main electrical supply.
5. Instrucións de funcionamento
The Vantec EEI 25-40/180 pump features an electronic control panel for easy operation and monitoring.
5.1. Initial Start-up and Auto-Adaptive Function
The pump is equipped with an auto-adaptive function, allowing it to start without requiring manual adjustments. It automatically and continuously adjusts its power to the system's needs through a permanent magnet motor and differential pressure regulator.
5.2. Electronic Control Panel
The electronic control panel is located on the top of the motor. Its digital display shows the current energy consumption in watts (W) or meters (m) of head. Use the control buttons to navigate through settings or modes if available (specific button functions are typically detailed in a separate quick start guide or on the device itself).

Imaxe: Primeiro plano view of the electronic control panel, highlighting the digital display and control buttons for monitoring and adjusting pump operation.
5.3. Applicable Systems
This circulation pump is suitable for a variety of applications, including:
- Sistemas de calefacción central
- Sistemas de calefacción por chan radiante
- Heating systems with constant temperature and variable flow
- Heating systems with night operation mode
- Sistemas de aire acondicionado
- Industrial circulation systems
- Domestic central heating (CO) systems
- Domestic hot water systems
6. Mantemento
The Vantec EEI 25-40/180 pump is designed for minimal maintenance due to its robust construction and corrosion-resistant materials. Regular checks can help ensure optimal performance and longevity.
- Inspección visual: Inspeccione periodicamente a bomba e as conexións para detectar calquera sinal de fugas, corrosión ou danos.
- Limpeza: Ensure the area around the pump is free from debris that could obstruct ventilation or access.
- Calidade da auga do sistema: Maintaining good system water quality (e.g., proper pH, inhibitors) can extend the life of the pump and the entire heating system.
For any internal maintenance or repairs, it is recommended to contact a qualified service technician.
7 Solución de problemas
If the pump is not operating as expected, consider the following basic checks:
- Sen enerxía: Check if the pump is properly plugged into a live electrical outlet. Verify circuit breakers or fuses.
- No Flow/Low Flow: Ensure all valves in the system are open. Check for air in the system and bleed if necessary. Verify that the system pressure is within the pump's operating range.
- Ruído inusual: Air in the system or debris in the pump can cause noise. Bleed the system or, if persistent, contact service personnel.
For complex issues or if basic troubleshooting does not resolve the problem, contact a qualified service technician or the manufacturer's support for assistance.
8. Especificacións
| Característica | Especificación |
|---|---|
| Voltage | 230 V / 50 Hz |
| Consumo de enerxía | 5 - 22 W |
| Caudal máximo | 48 l/min |
| Cabeza máxima | 4.5 m |
| Presión máxima de funcionamento | 10 bar |
| Temperatura de funcionamento | +2 °C a +110 °C |
| Spacing (Port-to-Port) | 180 mm |
| Diámetro de conexión | 1 1/2" - 1" |
| Índice de protección | IP44 |
| Dimensións (L x W x H) | 23 x 20 x 13 cm |
| Peso | 2.35 kg |
| Enrolamento do motor | 100% cobre |
9. Garantía e soporte
The Vantec EEI 25-40/180 Circulation Pump is covered by a manufacturer's warranty. Please refer to the warranty documentation provided with your purchase for specific terms and conditions. For technical support, service, or warranty claims, please contact your retailer or the Vantec customer service department. Keep your proof of purchase for warranty validation.





