waveshare 4-CH RS485 TO POE ETH (B)

Manual de instrucións do servidor serie Ethernet Waveshare de 4 canles RS485 a RJ45 (modelo RS485 de 4 canles a POE ETH (B))

Guía completa para a configuración, o funcionamento e o mantemento.

1. Introdución

The waveshare 4-Ch RS485 to RJ45 Ethernet Serial Server, Model 4-CH RS485 TO POE ETH (B), is a multi-functional industrial device designed for data acquisition and IoT gateway applications. It features four independent RS485 channels, allowing for effective and isolated data transmission. This module integrates functionalities such as a serial server, Modbus gateway, MQTT gateway, and RS485 to JSON conversion, making it suitable for diverse industrial network environments. Its robust design includes power supply and signal isolation, along with comprehensive protection features, ensuring stable and reliable operation.

Vídeo 1: Acabadoview of the waveshare 4-Ch RS485 to RJ45 Ethernet Serial Server. This video demonstrates the device's key features and applications, highlighting its multi-functional capabilities and robust design for industrial use.

2. Contido do paquete

Ao desembalar, comproba que se inclúen todos os seguintes elementos:

  • 1x 4-CH RS485 TO POE ETH (B) Module
  • 1x Rail-mount buckle
  • 1 x Destornillador
  • 1x Screws pack (4 screws)
Package contents of the waveshare 4-Ch RS485 to RJ45 Ethernet Serial Server

Imaxe 1: Illustration of the waveshare 4-Ch RS485 to RJ45 Ethernet Serial Server and its included accessories, such as the rail-mount buckle, screwdriver, and screws.

3. Features at a Glance

The 4-Ch RS485 to RJ45 Ethernet Serial Server offers a comprehensive set of features for industrial communication needs:

  • Independent RS485 Channels: Four RS485 channels operate independently, ensuring efficient and isolated data transmission without mutual interference.
  • Multi-functional Integration: Combines serial server, Modbus gateway, MQTT gateway, and RS485 to JSON functionalities.
  • Stable Power Input: Utilizes a screw terminal for reliable and stable power connection.
  • Montaxe flexible: Supports both wall-mount and rail-mount installations for quick deployment and expansion in industrial settings.
  • Industrial Isolation: Features power isolation and signal isolation for enhanced reliability and anti-interference.
  • PoE Ethernet Port: Includes a Power over Ethernet (PoE) enabled RJ45 port for simplified power and data connectivity (PoE version only).
  • Multi-Host Support: Designed to prevent crosstalk while communicating with multiple network devices.
  • Configurable: Soportes web browser configuration, DHCP, DNS, and device management functions library.
Key features of the waveshare 4-Ch RS485 to RJ45 Ethernet Serial Server

Imaxe 2: Visual representation of the core features, including industrial isolation, rail-mount capability, Modbus gateway, 4-channel independent RS485, and multiple power supply methods.

4. Especificacións

Detailed technical specifications for the 4-CH RS485 TO POE ETH (B) module:

CategoríaEspecificación
Tipo de produtoSerial server, Modbus Gateway, MQTT Gateway
Función básicaBi-directional transparent data transmission between RS485 and Ethernet
Interface de comunicaciónRS485 port x 4, Ethernet port x 1
Fonte de alimentaciónDC 6 - 45V screw terminal, or PoE port
Protección de illamentoPower isolation, Signal isolation
EthernetRJ45 10 / 100M auto-negotiation, 2 KV surge protection, IEEE 802.3af compliant (PoE)
Porto serieIsolated RS485 (4 channels can receive and transmit independently)
velocidade en baudios300 - 115200 bps
Bit de paridadeNone, odd, even, mark, space
Bit de datos5 - 9 bits
Control de fluxoN/A
ProtocoloETHERNET, IP, TCP, UDP, HTTP, ARP, ICMP, DHCP, DNS
ConfiguraciónHost, web browser, device management functions library
Método de comunicaciónTCP/IP direct communication, VCOM
Modo de funcionamentoTCP server, TCP client (coexisting with TCP server), UDP, UDP multicast
Temperatura de funcionamento-40 °C ~ 85 °C
Rango de humidade5% - 95% relative humidity
DimensiónsL × W × H: 91.0 × 64.5 × 24.2 mm
Peso do elemento7.4 onzas
Detailed specifications table for the waveshare serial server

Imaxe 3: A comprehensive table outlining the technical specifications and version options for the waveshare 4-Ch RS485 to RJ45 Ethernet Serial Server.

5. Configuración

Follow these steps to set up your waveshare 4-Ch RS485 to RJ45 Ethernet Serial Server:

5.1. Conexión de alimentación

  • Entrada de alimentación DC: Connect a DC 6-45V power supply to the V+ and V- screw terminals. Ensure correct polarity.
  • PoE (Power over Ethernet): If using the PoE version, connect a PoE-enabled Ethernet cable to the RJ45 port. This will provide both power and data connectivity.

5.2. Conexión de rede

  • Connect a standard RJ45 Ethernet cable from your network switch or router to the Ethernet port on the module.
  • The module defaults to static IP addresses in the range of 192.168.1.200-192.168.1.204. It is recommended to initially set up the device on an isolated network to avoid IP conflicts.

5.3. RS485 Device Connection

  • Connect your RS485 devices to the corresponding A+, B-, and Signal Ground terminals for each of the four RS485 channels.
  • Ensure correct wiring polarity (A+ to A+, B- to B-) for proper communication.

5.4. Configuración inicial

  • Access the device's configuration interface via a web browser by entering its default IP address (e.g., 192.168.1.200).
  • Alternatively, use the provided VirCom software (available from the Waveshare Wiki) to discover and configure the device on your network.
  • You can change the IP settings to DHCP or assign a static IP within your network range.
Wiring and power options for the waveshare serial server

Imaxe 4: Diagram illustrating the primary function of bi-directional data transmission, multi-power supply options (PoE and screw terminal), and the industrial rail-mount design.

6. Instrucións de funcionamento

The 4-Ch RS485 to RJ45 Ethernet Serial Server supports various operating modes and protocols:

6.1. Multi Communication Modes

  • TCP Server: Supports up to 30 concurrent TCP connections. The module listens on configured ports, and data from serial devices is transferred to connected TCP clients.
  • TCP Client: Allows concurrent connection to up to 7 target IPs. It can also function as a server simultaneously, supporting 22 concurrent client connections. It establishes bi-directional transparent transfer between the server and serial device.
  • UDP Multicast: In UDP multicast mode, the module sends and receives data to and from a multicast group, reducing network load.
  • Modo UDP: The module communicates with specific IP and port numbers, improving data transfer accuracy.

6.2. Modbus Gateway Support

The module functions as a Modbus gateway, facilitating communication between Modbus TCP and Modbus RTU devices. This is ideal for upgrading Modbus networking infrastructure.

6.3. MQTT/JSON to Modbus Conversion

When used as an MQTT gateway, the device can upload serial data to an MQTT server via transparent transmission. It supports various cloud platforms. Acquired Modbus RTU or non-standard serial data can be parsed into JSON format and packaged into MQTT data packets for uploading. As a JSON data acquisition gateway, it can connect to data acquisition instruments via RS485, acquire data, convert it to JSON, and post it to a server. The uploaded data format can be configured via host, and the JSON upload protocol can be MQTT, HTTP POST, HTTP GET, etc.

6.4. Multi Hosts Roll-Polling Support

This feature ensures that different network devices are identified and responded to respectively, preventing crosstalk when communicating with multiple network devices.

6.5. User-Defined Heartbeat/Registration Packet

Facilitates easy cloud communication and device identification through user-defined heartbeat and registration packets.

6.6. NTP Protocol Support

Supports Network Time Protocol (NTP) for obtaining network time information or for data upload synchronization.

6.7. Multi Configuration Methods

The module can be configured using various methods, including a web browser interface, obtaining dynamic IP via DHCP, and DNS protocol connected domain server address. A device management functions library is also available.

Advanced communication features of the waveshare serial server

Imaxe 5: Visual acabadoview of advanced features such as MQTT/JSON to Modbus conversion, multi-host roll-polling, NTP protocol support, and various configuration methods.

7. Introdución á interface

Understanding the physical interfaces and indicators is crucial for proper operation:

7.1. Physical Interfaces

  • Botón RST: Úsase para restablecer o dispositivo á configuración predeterminada de fábrica.
  • DC 6-45V Power Input: Screw terminals for connecting external DC power (V+, V-).
  • RS485 Ports (1-4): Each port has A+, B-, and Signal Ground terminals for connecting RS485 devices.
  • PoE ETH Port: RJ45 connector for Ethernet and Power over Ethernet (PoE) input.

7.2. Descrición do indicador

  • PWR (Power Indicator): Ilumínase cando o dispositivo está acendido.
  • NET (Network Indicator): Blinks when connected to the Ethernet network.
  • LINKx (Link Indicator): Lights up when a connection is established on the corresponding RS485 channel (x=1, 2, 3, 4).
  • ACTx (Activity Indicator): Lights up when data is being transmitted on the corresponding RS485 channel (x=1, 2, 3, 4).
Interface layout and LED indicators of the waveshare serial server

Imaxe 6: Detallado view of the device's interfaces, including the reset button, power input, RS485 terminals, Ethernet port, and a description of the LED indicators (PWR, NET, LINKx, ACTx).

8. Multiple Protection, Safe And Stable

The module is designed with multiple protection mechanisms to ensure high reliability and strong anti-interference capabilities:

  • Digital Isolation: Provides isolation for digital signals.
  • Protección ESD: Electrostatic Discharge protection.
  • Protección contra sobrecorriente: Protección contra a corrente excesiva.
  • Sobrevoltage Protección: Protexe contra o volumetage picos.
  • TVS Protection: Built-in Transient Voltage Suppression (TVS) tube effectively suppresses surge voltage and transient peak voltage no circuíto.
  • Resettable Fuse & Protection Diode: Ensures stable output of current and voltage, preventing over-current and over-voltage, and improving shock-proof performance.

9. Aluminium Alloy Enclosure

The device features a durable aluminum alloy enclosure with sandblasting and anodic oxidation treatment. This robust construction provides solid protection, a good hand feeling, and supports both wall-mount and rail-mount installations for industrial environments.

10. Dimensións do contorno

The physical dimensions of the module are as follows:

  • Lonxitude (L): 91.0 mm
  • Ancho (W): 64.5 mm
  • Altura (H): 24.2 mm
Outline dimensions and customization options for the waveshare serial server

Imaxe 7: Diagram showing the precise outline dimensions of the module in millimeters, along with information on batch customization support.

11. Mantemento

To ensure the longevity and optimal performance of your waveshare 4-Ch RS485 to RJ45 Ethernet Serial Server, consider the following maintenance guidelines:

  • Inspección periódica: Periodically check all cable connections (power, Ethernet, RS485) to ensure they are secure and free from damage.
  • Control ambiental: Operate the device within the specified operating temperature (-40°C ~ 85°C) and humidity (5% - 95% relative humidity) ranges. Avoid exposure to extreme conditions, dust, and moisture.
  • Limpeza: Keep the device clean and free from dust accumulation. Use a soft, dry cloth for cleaning. Do not use liquid cleaners.
  • Actualizacións de firmware: Check the official Waveshare website or Wiki periodically for any available firmware updates. Applying updates can improve performance, add features, or fix bugs.
  • Ciclo de potencia: If the device becomes unresponsive, perform a power cycle (disconnect and reconnect power) as a first troubleshooting step.

12 Solución de problemas

This section addresses common issues you might encounter with the waveshare 4-Ch RS485 to RJ45 Ethernet Serial Server:

12.1. Sen alimentación / LED de alimentación apagado

  • Comprobar a fonte de alimentación: Ensure the DC 6-45V power supply is correctly connected to the screw terminals and is providing the correct voltage.
  • Comprobar PoE: If using PoE, verify that the Ethernet cable is connected to a PoE-enabled port on your switch/injector and that the PoE source is active.
  • Inspeccionar o cableado: Confirm that the power wires are securely fastened in the screw terminals and that there are no shorts or breaks.

12.2. No Network Connectivity / NET LED Not Blinking

  • Cable Ethernet: Ensure the RJ45 Ethernet cable is securely connected to both the module and your network device. Try a different cable.
  • Configuración da rede: The device defaults to static IPs (192.168.1.200-192.168.1.204). Ensure your PC is on the same subnet (e.g., 192.168.1.x) to access the web interface or use the VirCom software.
  • IP Conflicts: If other devices on your network use the default IPs, configure the module on an isolated network first, then change its IP settings.
  • DHCP Settings: If configured for DHCP, ensure a DHCP server is available on your network.

12.3. RS485 Communication Failure / ACTx LED Not Blinking

  • Cableado: Double-check the RS485 wiring (A+ to A+, B- to B-) between the module and your serial devices. Ensure Signal Ground is also connected if required.
  • Serial Parameters: Verify that the baud rate, parity bit, and data bit settings on the module match those of your connected RS485 devices.
  • Enderezo do dispositivo: For Modbus or other protocols, ensure correct device addressing and commands are being used.
  • Illamento: While the module provides isolation, ensure external RS485 devices are also properly isolated or grounded to prevent ground loops.

12.4. Cannot Access Configuration Interface

  • IP predeterminada: Confirm you are using the correct default IP address (e.g., 192.168.1.200) or the IP you previously assigned.
  • Conexión de rede: Ensure your PC is on the same subnet as the module.
  • VirCom Software: Use the Waveshare VirCom software to discover the device's IP address if it's unknown.
  • Firewall: Temporarily disable your computer's firewall to rule out blocking access.
  • Restablecer: If all else fails, press the RST button to restore factory default settings (this will reset the IP to default).

For more detailed troubleshooting and advanced configurations, please refer to the official Waveshare Wiki for the 4-CH RS485 TO POE ETH (B) module.

13. Garantía e soporte

This waveshare product is designed for reliability and performance. For specific warranty terms and conditions, please refer to the purchase documentation or contact your vendor. Waveshare provides technical support and resources to assist with product usage and troubleshooting.

13.1. Soporte técnico

For technical assistance, detailed documentation, and software downloads, please visit the official Waveshare website or their product Wiki. The Wiki often contains comprehensive guides, examples, and FAQs that can help resolve complex issues.

13.2. Información de contacto

You can typically find contact information for Waveshare support on their official website. Please have your product model (4-CH RS485 TO POE ETH (B)) and any relevant purchase details ready when seeking support.

Documentos relacionados - 4-CH RS485 TO POE ETH (B)

Preview Waveshare RS485 TO ETH (B) User Manual - Industrial RS485 to Ethernet IoT Gateway
Comprehensive user manual for the Waveshare RS485 TO ETH (B), an industrial serial device server and IoT gateway. Learn about its features, applications, configuration, and how to connect RS485 devices to Ethernet for Modbus, MQTT, and cloud integration.
Preview Manual do usuario de Waveshare UART a ETH (B): Guía do conversor de serie a Ethernet
Manual de usuario completo para o módulo Waveshare UART TO ETH (B), que detalla as súas características como conversor UART a Ethernet, pasarela de IoT, pasarela Modbus e servidor serie para aplicacións industriais.
Preview Especificación técnica da pasarela Ethernet RS232/RS485 a Ethernet e PoE
Este documento proporciona especificacións detalladas, características de hardware e software e procedementos de proba para as pasarelas Waveshare RS232/RS485 a Ethernet e PoE Ethernet. Estes dispositivos funcionan como servidores serie, pasarelas Modbus e pasarelas MQTT para a adquisición de datos industriais e a conectividade IoT.
Preview Waveshare RS232/485 to Ethernet Converter User Manual
This is an industrial-grade RS232/485 to Ethernet module from Waveshare, enabling bidirectional transparent data transmission between RS232, RS485, and RJ45 Ethernet ports. It features a 32-bit ARM M4 processor, 10/100M Ethernet, multiple operating modes (TCP Server/Client, UDP, HTTPD), Modbus gateway, and Websocket support, offering high speed, low power consumption, and stability for industrial IoT applications.
Preview Manual do usuario da comunicación Waveshare RS485 a WiFi/ETH MQTT
Manual de usuario completo para o módulo Waveshare RS485 a WiFi/ETH, que guía aos usuarios a través da preparación do software e hardware, a configuración da rede e o establecemento da comunicación MQTT con plataformas como EMQX.
Preview Manual do usuario do servidor serie Waveshare RS232/485 a WiFi PoE Ethernet (B)
Explora o Manual do usuario de Waveshare RS232/485 a WiFi PoE Ethernet (B), unha guía completa para o servidor serie que converte interfaces de rede RS232/485 a TCP/IP, o que permite a transmisión de datos bidireccional a través de WiFi e Ethernet.