KMC CONTROLS STE-9000 series NetSensor Damage from Incorrect

Especificacións
- Product: STE-9000 series NetSensor
- Features: Temperature and humidity readings
- Model: All STE-9000 series NetSensors
Instrucións de uso do produto
- Ensure that both tabs on the sensor cover rest on top of the backplate.
- Make sure the anti-tamper hex screw is fully rotated into the backplate before installing or uninstalling the sensor cover.
- Swing the cover from the top onto the backplate.
- Do NOT push the cover directly onto the plate or swing it from the bottom.
- If any force seems to be needed, check the alignment of the tabs on the top of the backplate and/or the anti-tamper screw before swinging the sensor cover onto the backplate.
- For more detailed installation instructions, please refer to the STE-9000 Series NetSensors Installation Guide.
Complete os seguintes pasos para montar un NetSensor dixital da serie KMC Conquest STE-9000 e conécteo a un controlador Conquest BAC-59xx/9xxx.

NOTA: Vexa o Conquest NetSensors STE- 9000 Series Digital Room Sensors ficha técnica e o Guía de selección de conquistas at kmccontrols.com for specifications and other information.
AVISO
- OBSERVE AS PRECAUCIÓNS PARA A MANIPULACIÓN DE DISPOSITIVOS SENSIBLE A ELECTROSTÁTICA
SELECCIONAR LUGAR DE MONTAXE
- Vexa o Localización de montaxe de sensores de sala e termostatos e guía de aplicacións de mantemento for cautions, troubleshooting, and best practices.
NOTA: Complete o cableado en cada lugar antes de instalar un sensor.
ELIMINAR A PLACA POSTERIOR
- Turn the hex screw(1) clockwise into the sensor until the screw clears the cover.

NOTA: The hex screw(2_ should remain in the backplate.
- Tire da tapa da placa posterior.
CONECTAR CABLE DE ETHERNET - Feed the Ethernet patch cable(3) from the Conquest controller through the center of the backplate(4).
NOTA: O cable de conexión Ethernet debe ter un máximo de 150 pés (45 metros).
- Monte a placa posterior nunha caixa eléctrica usando os parafusos proporcionados.
NOTA: If additional thermal insulation is needed, install the optional HPO-9002 gasket before installing the backplate.
Para obter máis información, consulte o Room Sensor and Thermostat Mou
nting Location and Maintenance Application Guide. - Enchufe o cable Ethernet 5 na toma modular 6 do sensor.
INSTALAR A CUBIERTA DO SENSOR - Place the cover(7) over the top of the backplate(8) and swing it down.
NOTA: Teña coidado de non pinchar o cable Ethernet.
- Turn the hex screw(9) counterclockwise until it engages the cover.

OPERAR
- The STE-9000 Series NetSensor becomes operational after it is connected to a powered Conquest controller.
- NOTA: To change setpoints or configuration, see the Guía de aplicación do controlador KMC Conquest.
- NOTA: For continued maximum NetSensor efficiency, see the maintenance section in the Localización de montaxe de sensores de sala e termostatos e guía de aplicacións de mantemento.
AVISOS IMPORTANTES
- O material deste documento é só para fins informativos. O contido e o produto que describe están suxeitos a cambios sen previo aviso.
- KMC Controls, Inc. makes no representations orwarranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct, or indirect, arising out of or related to the use of this document.
- O logotipo de KMC é unha marca rexistrada de KMC Controls, Inc. Todos os dereitos reservados.
CONTACTO
- TELÉFONO: 574.831.5250
- FAX: 574.831.5252
- correo electrónico: info@kmccontrols.com
FAQ
Q: Which models are affected by the installation issue?
A: This issue affects all STE 9000 series NetSensors.
Q: What are the potential errors from a damaged printed circuit board?
A: Incorrect temperature and humidity readings may result from a damaged printed circuit board.
Documentos/Recursos
![]() |
KMC CONTROLS STE-9000 series NetSensor Damage from Incorrect Installation [pdfGuía do usuario STE-9000 series NetSensor Damage from Incorrect Installation, STE-9000 series, NetSensor Damage from Incorrect Installation, NetSensor Damage from Incorrect Installation, NetSensor Damage, from Incorrect Installation |